<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE ArticleSet PUBLIC "-//NLM//DTD PubMed 2.7//EN" "https://dtd.nlm.nih.gov/ncbi/pubmed/in/PubMed.dtd">
<ArticleSet>
<Article>
<Journal>
				<PublisherName>Shahid Beheshti University</PublisherName>
				<JournalTitle>International Journal of Research and Technology in Electrical Industry</JournalTitle>
				<Issn>2821-0190</Issn>
				<Volume>2</Volume>
				<Issue>1</Issue>
				<PubDate PubStatus="epublish">
					<Year>2023</Year>
					<Month>05</Month>
					<Day>08</Day>
				</PubDate>
			</Journal>
<ArticleTitle>A New Approach to AC Microgrids Protection Using a Bi-Level Multi-Agent System</ArticleTitle>
<VernacularTitle></VernacularTitle>
			<FirstPage>58</FirstPage>
			<LastPage>66</LastPage>
			<ELocationID EIdType="pii">102279</ELocationID>
			
<ELocationID EIdType="doi">10.52547/ijrtei.1.1.66</ELocationID>
			
			<Language>EN</Language>
<AuthorList>
<Author>
					<FirstName>Navid</FirstName>
					<LastName>Ghaffarzadeh</LastName>
<Affiliation>Imam Khomeini International University, Qazvin, Iran</Affiliation>
<Identifier Source="ORCID">0000-0001-5552-9866</Identifier>

</Author>
<Author>
					<FirstName>Ali</FirstName>
					<LastName>Bamshad</LastName>
<Affiliation>Imam Khomeini International University, Qazvin, Iran</Affiliation>
<Identifier Source="ORCID">0000-0001-7388-4183</Identifier>

</Author>
</AuthorList>
				<PublicationType>Journal Article</PublicationType>
			<History>
				<PubDate PubStatus="received">
					<Year>2023</Year>
					<Month>01</Month>
					<Day>17</Day>
				</PubDate>
			</History>
		<Abstract>Nowadays, microgrids are expanding due to their numerous benefits. However, the control and protection of microgrids is a serious challenge. All the implemented plans for the protection of microgrids have drawbacks. This study presents a bi-level multi-agent system (MAS) approach to microgrids protection. The first level is responsible for microgrid lines protection. Firstly, it calculates the pilot impedance of each line. For line’s internal faults, pilot impedance is a limited number, but for line’s external faults, it will be infinite. so, the line’s internal fault is detected by evaluation of pilot impedance with a predetermined value. The second level is responsible for Distributed Generation (DGs) protection. Firstly, it decomposes the DGs output signals by Discrete Wavelet Transform (DWT). Then, it multiplies the summations of the first and second level’s details of each signal together as CC index. CC is zero in normal grid conditions and has a negative peak with a sharp negative rate in external faults, and will experience a positive peak with a sharp positive rate for internal faults and changes with a very slow rate in case of grid’s natural transitions. So, the agent detects the fault by evaluating the CC. The simulation results in a 5-bus microgrid indicate the proposed scheme protects the microgrid with a reliability of 100% with considering all microgrid’s uncertainties.</Abstract>
		<ObjectList>
			<Object Type="keyword">
			<Param Name="value">Microgrid protection</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">Bi-level MAS</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">Pilot impedance</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">Symlet DWT</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">Resilience</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">Uncertain parameters</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">DG</Param>
			</Object>
		</ObjectList>
<ArchiveCopySource DocType="pdf">https://ijrtei.sbu.ac.ir/article_102279_51837925fa3567e7e97c71de9f2a49bd.pdf</ArchiveCopySource>
</Article>
</ArticleSet>